Device parameters

Configurable parameters

Parameter name and designation

Modbus address

Modbus function

Write / Read

Hash-code

Format, data size

Range of values and indication

Factory settings

Setpoint 1

U1

0×000C

0×000D

0×06, 0×10 / 0×03

0×FA1E

Long

(4 bytes)

from minus 99999 to 999999

999999

Setpoint 2

U2

0×000E

0×000F

0×06, 0×10 / 0×03

0×9707

Long

(4 bytes)

from minus 99999 to 999999

0

Counting mode

inP

0×0008

0×06, 0×10 / 0×03

0×38D9

Word

(2 bytes)

0 – Count-up (1)

Count-up

1 – Count-down (2)

2 – Command (3)

3 – Individual (4)

4 – Reversing (5)

5 – Quadrature (6)

Output mode

oUt

0×0009

0×06, 0×10 / 0×03

0×D11F

Word

(2 bytes)

0 – Switched after setpoint (1)

Switched after setpoint

1 – Switched before setpoint (2)

2 – Switched for a time after the setpoint (3)*

3 – Switched when multiple setpoint values (4)

Notice
* After reaching the setpoint the output is switched for a time period, that is specified in parameteres t1  and t2, the count value is reset and the counting continues from zero (parameter SPM = RESET).

Time period for output 1

t1

0×0010

0×0011

0×06, 0×10 / 0×03

0×2E75

Unsigned long

(4 bytes)

from 0 to 999990 ms

1000 ms

Time period for output 2

t2

0×0012

0×0013

0×06, 0×10 / 0×03

0×436C

Unsigned long

(4 bytes)

from 0 to 999990 ms

1000 ms

Decimal point position multiplier

FDP
0×0014 0×06, 0×10 / 0×03 0×6ABF

Word

(2 bytes)

0 (------)

0

1 (-----.-)

2 (----.--)

3 (---.---)

4 (--.----)

5 (-.-----)

Multiplier

F

0×0015

0×0016

0×06, 0×10 / 0×03

0×3085

Unsigned long

(4 bytes)

from 0.00001 to 99999

1

Position of the decimal point

DP

0×0007

0×06, 0×10 / 0×03

0×B3EB

Word

(2 bytes)

0 (------)

0

1 (-----.-)

2 (----.--)

3 (---.---)

4 (--.----)

Type of work after reaching setpoint

SPM

0×000A

0×06, 0×10 / 0×03

0×69B2

Word

(2 bytes)

0 – Continue counting without resetting(CONT)

Continue counting without resetting

1 – Stop the counting until a "RESET" signal

(STOP)

2 – Reset the counter and continue counting

(RESET)

Type of work to "Reset" signal

rSt

0×000B

0×06, 0×10 / 0×03

0×4C9A

Word

(2 bytes)

0 – Reset the counter(1)

Reset the counter

1 – Reset the counter and disable output signals (2)

2 – Reset the counter and wait for signal "Start" (3)

3 – Reset the counter and wait for signal "Stop" (4)

Frequency of the input filter

FREQ

0×0017

0×06, 0×10 / 0×03

0×9FE6

Word

(2 bytes)

from 1 to 50000 Hz

50000 Hz

Minimum duration of the signal on the control inputs

Cnt.t

0×0018

0×0019

0×06, 0×10 / 0×03

0×5C98

Unsigned long

(4 bytes)

from 10 to 9999990 microseconds

10 microseconds

Input logic1)

(type of input signal)

SiG

0×001D

0×06, 0×10 / 0×03

0×601C

Word

(2 bytes)

0 – nPn

nPn

1 – PnP

Brightness of the indicator

brHt

0×001C

0×06, 0×10 / 0×03

0×0AE6

Word

(2 bytes)

from 0 to 3 (14)

3

Lock buttons

LoCK

0×001A

0×06, 0×10 / 0×03

0×E954

Word

(2 bytes)

0 – Buttons unlocked

(oFF)

Buttons unlocked

1 – Blocked counter reset (1)

2 – Change of setpoints is blocked

(2)

3 – Reset and change of setpoints are blocked (3)

Restore factory settings

dEFAUL

YES / no

Password

PASS

0×001E

0×06, 0×10 / 0×03

0×2728

Word

(2 bytes)

from 0000 to 9999

0000

Displayed setpoint2)

ind2

0×001B

0×06, 0×10 / 0×03

0×CAA0

Word

(2 bytes)

0 – Setpoint 1

0

1 – Setpoint 2

Command for applying settings2)

APPL

1 – Exit with saving

2 – Exit without saving

3 – Return to factory settings

RS-485 settings

RS-485 data transfer rate

bPS

0×0000

0×06, 0×10 / 0×03

0×B760

Word

(2 bytes)

0 – 2400

9600

1 – 4800
2 – 9600

3 – 14400; 4 – 19200

5 – 28800; 6 – 38400

7 – 57600; 8 – 115200

Data word length

LEn

0×0001

0×06, 0×10 / 0×03

0×523F

Word

(2 bytes)

0 – 7 bit (7 bit)

8 bit

1 – 8 bit (8 bit)

Parity

PrtY

0×0002

0×06, 0×10 / 0×03

0×E8C4

Word

(2 bytes)

0 – Without parity (NO)

Without parity

1 – Even parity

(EVEN)

2 – Odd parity (Odd)

Number of stop bits

Sbit

0×0003

0×06, 0×10 / 0×03

0×B72E

Word

(2 bytes)

0 – 1 stop bit

1 stop bit

1 – 2 stop bits

Base address of the device3)

Addr

0×0005

0×06, 0×10 / 0×03

0×9F62

Word

(2 bytes)

from 0 to 255 when A.Len = 8

16

from 0 до 2047 when A.Len =  11

Length of network address2)

A.LEN

0×0004

0×06, 0×10 / 0×03

0×1ED2

Word

(2 bytes)

8 bit

8 bit

11 bit

Response delay

RS-485

rS.dL

0×0006

0×06, 0×10 / 0×03

0×CBF5

Word

(2 bytes)

from 0 to 45

0

Notes

1) Setting of parameter SiG works only together with DIP switch (see section).

2) Parameters that are not displayed in the Setup mode of the device.

3) In Modbus protocol address 0 is reserved for broadcast packages. In OWEN protocol address 255 is reserved for broadcast packages.

Readable parameters

Designation and parameter name

Modbus address

Modbus function

Read-only

Hash-code

Format and size of data

Note

Current value of the pulse counter Ctr

0×0000

0×0001

0×04

0×A158

Long (4 bytes)

Current counter value in physical units CEU

0×0002

0×0003

0×04

0×B8BC

Long (4 bytes)

Current status of the "Start/stop"

StSt

0×0004

0×04

0×6577

0 – start;

1 – stop

Current mode (count, setup)

CUR

0×0005

0×04

0×CC41

Word (2 bytes)

0 – count (password not required);

1 – setup from the device's buttons;

2 – setup from the PC;

3 – count (requires password)

Network error code on last access

to the device

n.Err

0×0006

0×04

0×0233

Word (2 bytes)

From 0 to 255.

After turning on the device – 0

Name of the device

DEV

0×0007

0×0008

0×04

0×D681

ASCII string

(4 bytes)

Software version

VER

0×0009

0×000А

0×04

0×2D5B

ASCII string

(4 bytes)

X.YY,

where Х – number of version, YY – number of subversion

Bit parameters

Designation and name of parameter

Modbus address

Modbus function

write / read

Hash-code

Format and size of data

Note

Digital inputs

Current status of the "Reset" input

rSti

0×0000

– / 0×02

0×C010

Byte (1 byte)

0 / 1

Current status of the "Block" input

Loci

0×0001

– / 0×02

0×93EC

Byte (1 byte)

0 / 1

Digital outputs

Status of output 1

OSt1

0×0000

– / 0×01

0×6FFD

Byte (1 byte)

0 / 1

Status of output 2

OSt2

0×0001

– / 0×01

0×52A1

Byte (1 byte)

0 / 1

Reset of counter

rStC

0×0002

0×05, 0×0F / 0×01

0×DF1F

Byte (1 byte)

0 / 1

0 – no action;

1 – reset

Enable/disable the program control mode counter START/STOP

OnOff

0×0003

0×05 / –

0 – OFF (0x0000);

1 – ON (0xFF00)

Command to set the program control mode counter START/STOP

PStSt

0×0004

0×05 / –

0 – STOP (0x0000);

1 – START (0xFF00)