Configurable parameters
Parameter name and designation |
Modbus address |
Modbus function Write / Read |
Hash-code |
Format, data size |
Range of values and indication |
Factory settings |
---|---|---|---|---|---|---|
Setpoint 1 U1 | 0×000C 0×000D | 0×06, 0×10 / 0×03 | 0×FA1E | Long (4 bytes) | from minus 99999 to 999999 |
999999 |
Setpoint 2 U2 | 0×000E 0×000F | 0×06, 0×10 / 0×03 | 0×9707 | Long (4 bytes) | from minus 99999 to 999999 |
0 |
Counting mode inP | 0×0008 | 0×06, 0×10 / 0×03 | 0×38D9 | Word (2 bytes) | 0 – Count-up (1) | Count-up |
1 – Count-down (2) | ||||||
2 – Command (3) | ||||||
3 – Individual (4) | ||||||
4 – Reversing (5) | ||||||
5 – Quadrature (6) | ||||||
Output mode oUt | 0×0009 | 0×06, 0×10 / 0×03 | 0×D11F | Word (2 bytes) | 0 – Switched after setpoint (1) | Switched after setpoint |
1 – Switched before setpoint (2) | ||||||
2 – Switched for a time after the setpoint (3)* | ||||||
3 – Switched when multiple setpoint values (4) | ||||||
Notice *
After reaching the setpoint the output is switched for a time period,
that is specified in parameteres t1 and t2, the count value is reset and the counting continues
from zero (parameter SPM = RESET). | ||||||
Time period for output 1 t1 | 0×0010 0×0011 | 0×06, 0×10 / 0×03 | 0×2E75 | Unsigned long (4 bytes) | from 0 to 999990 ms | 1000 ms |
Time period for output 2 t2 | 0×0012 0×0013 | 0×06, 0×10 / 0×03 | 0×436C | Unsigned long (4 bytes) | from 0 to 999990 ms | 1000 ms |
Decimal point position multiplier FDP | 0×0014 | 0×06, 0×10 / 0×03 | 0×6ABF | Word (2 bytes) | 0 (------) | 0 |
1 (-----.-) | ||||||
2 (----.--) | ||||||
3 (---.---) | ||||||
4 (--.----) | ||||||
5 (-.-----) | ||||||
Multiplier F | 0×0015 0×0016 | 0×06, 0×10 / 0×03 | 0×3085 | Unsigned long (4 bytes) | from 0.00001 to 99999 | 1 |
Position of the decimal point DP | 0×0007 | 0×06, 0×10 / 0×03 | 0×B3EB | Word (2 bytes) | 0 (------) | 0 |
1 (-----.-) | ||||||
2 (----.--) | ||||||
3 (---.---) | ||||||
4 (--.----) | ||||||
Type of work after reaching setpoint SPM | 0×000A | 0×06, 0×10 / 0×03 | 0×69B2 | Word (2 bytes) | 0 – Continue counting without resetting(CONT) | Continue counting without resetting |
1 – Stop the counting until a "RESET" signal (STOP) | ||||||
2 – Reset the counter and continue counting (RESET) | ||||||
Type of work to "Reset" signal rSt | 0×000B | 0×06, 0×10 / 0×03 | 0×4C9A | Word (2 bytes) | 0 – Reset the counter(1) | Reset the counter |
1 – Reset the counter and disable output signals (2) | ||||||
2 – Reset the counter and wait for signal "Start" (3) | ||||||
3 – Reset the counter and wait for signal "Stop" (4) | ||||||
Frequency of the input filter FREQ | 0×0017 | 0×06, 0×10 / 0×03 | 0×9FE6 | Word (2 bytes) | from 1 to 50000 Hz | 50000 Hz |
Minimum duration of the signal on the control inputs Cnt.t | 0×0018 0×0019 | 0×06, 0×10 / 0×03 | 0×5C98 | Unsigned long (4 bytes) | from 10 to 9999990 microseconds | 10 microseconds |
Input logic1) (type of input signal) SiG | 0×001D | 0×06, 0×10 / 0×03 | 0×601C | Word (2 bytes) | 0 – nPn | nPn |
1 – PnP | ||||||
Brightness of the indicator brHt | 0×001C | 0×06, 0×10 / 0×03 | 0×0AE6 | Word (2 bytes) | from 0 to 3 (1 – 4) | 3 |
Lock buttons LoCK | 0×001A | 0×06, 0×10 / 0×03 | 0×E954 | Word (2 bytes) | 0 – Buttons unlocked (oFF) | Buttons unlocked |
1 – Blocked counter reset (1) | ||||||
2 – Change of setpoints is blocked (2) | ||||||
3 – Reset and change of setpoints are blocked (3) | ||||||
Restore factory settings dEFAUL | – | – | – | – | YES / no | – |
Password PASS | 0×001E | 0×06, 0×10 / 0×03 | 0×2728 | Word (2 bytes) | from 0000 to 9999 | 0000 |
Displayed setpoint2) ind2 | 0×001B | 0×06, 0×10 / 0×03 | 0×CAA0 | Word (2 bytes) | 0 – Setpoint 1 | 0 |
1 – Setpoint 2 | ||||||
Command for applying settings2) APPL | – | – | – | – | 1 – Exit with saving | – |
2 – Exit without saving | ||||||
3 – Return to factory settings | ||||||
RS-485 settings | ||||||
RS-485 data transfer rate bPS | 0×0000 | 0×06, 0×10 / 0×03 | 0×B760 | Word (2 bytes) | 0 – 2400 | 9600 |
1 – 4800 | ||||||
2 – 9600 | ||||||
3 – 14400; 4 – 19200 | ||||||
5 – 28800; 6 – 38400 | ||||||
7 – 57600; 8 – 115200 | ||||||
Data word length LEn | 0×0001 | 0×06, 0×10 / 0×03 | 0×523F | Word (2 bytes) | 0 – 7 bit (7 bit) | 8 bit |
1 – 8 bit (8 bit) | ||||||
Parity PrtY | 0×0002 | 0×06, 0×10 / 0×03 | 0×E8C4 | Word (2 bytes) | 0 – Without parity (NO) | Without parity |
1 – Even parity (EVEN) | ||||||
2 – Odd parity (Odd) | ||||||
Number of stop bits Sbit | 0×0003 | 0×06, 0×10 / 0×03 | 0×B72E | Word (2 bytes) | 0 – 1 stop bit | 1 stop bit |
1 – 2 stop bits | ||||||
Base address of the device3) Addr | 0×0005 | 0×06, 0×10 / 0×03 | 0×9F62 | Word (2 bytes) | from 0 to 255 when A.Len = 8 | 16 |
from 0 до 2047 when A.Len = 11 | ||||||
Length of network address2) A.LEN | 0×0004 | 0×06, 0×10 / 0×03 | 0×1ED2 | Word (2 bytes) | 8 bit | 8 bit |
11 bit | ||||||
Response delay RS-485 rS.dL | 0×0006 | 0×06, 0×10 / 0×03 | 0×CBF5 | Word (2 bytes) | from 0 to 45 | 0 |
Notes 1) Setting of parameter SiG works only together with DIP switch (see section). 2) Parameters that are not displayed in the Setup mode of the device. 3) In Modbus protocol address 0 is reserved for broadcast packages. In OWEN protocol address 255 is reserved for broadcast packages. |
Readable parameters
Designation and parameter name |
Modbus address |
Modbus function Read-only |
Hash-code |
Format and size of data |
Note |
---|---|---|---|---|---|
Current value of the pulse counter Ctr | 0×0000 0×0001 | 0×04 | 0×A158 | Long (4 bytes) | – |
Current counter value in physical units CEU |
0×0002 0×0003 | 0×04 | 0×B8BC | Long (4 bytes) | – |
Current status of the "Start/stop" StSt | 0×0004 | 0×04 | 0×6577 | – | 0 – start; 1 – stop |
Current mode (count, setup) CUR | 0×0005 | 0×04 | 0×CC41 | Word (2 bytes) | 0 – count (password not required); 1 – setup from the device's buttons; 2 – setup from the PC; 3 – count (requires password) |
Network error code on last access to the device n.Err | 0×0006 | 0×04 | 0×0233 | Word (2 bytes) | From 0 to 255. After turning on the device – 0 |
Name of the device DEV | 0×0007 0×0008 | 0×04 | 0×D681 | ASCII string (4 bytes) | – |
Software version VER |
0×0009 0×000А |
0×04 |
0×2D5B |
ASCII string (4 bytes) |
X.YY, where Х – number of version, YY – number of subversion |
Bit parameters
Designation and name of parameter | Modbus address | Modbus function write / read | Hash-code | Format and size of data | Note |
---|---|---|---|---|---|
Digital inputs | |||||
Current status of the "Reset" input rSti | 0×0000 | – / 0×02 | 0×C010 | Byte (1 byte) 0 / 1 | – |
Current status of the "Block" input Loci | 0×0001 | – / 0×02 | 0×93EC | Byte (1 byte) 0 / 1 | – |
Digital outputs | |||||
Status of output 1 OSt1 | 0×0000 | – / 0×01 | 0×6FFD | Byte (1 byte) 0 / 1 |
– |
Status of output 2 OSt2 | 0×0001 | – / 0×01 | 0×52A1 | Byte (1 byte) 0 / 1 |
– |
Reset of counter rStC | 0×0002 | 0×05, 0×0F / 0×01 | 0×DF1F | Byte (1 byte) 0 / 1 | 0 – no action; 1 – reset |
Enable/disable the program control mode counter START/STOP OnOff | 0×0003 | 0×05 / – | – | – | 0 – OFF (0x0000); 1 – ON (0xFF00) |
Command to set the program control mode counter START/STOP PStSt | 0×0004 |
0×05 / – |
– | – |
0 – STOP (0x0000); 1 – START (0xFF00) |